BEx1 IP67Ex IO module

Compact IO module for Ex Zone 1/21 with Profinet or Modbus TCP/IP.
The module include busnode, isolating amplifier and 32 intrinsically safe analog and digital IO channels on
smallest space.
The module can be installed directly in Zone 1/21 and connects sensors and actuators from Zone 0/20.

  • Full potting → etreme robust
  • Intrinsically safe IO channels 
  • None configuration on module required
  • Separate power supply for sensor and actuator
  • Comprehensive diagnostics for each channel
  • Open load detection
  • Prefault detection
  • Short circuit detection
  • Galvanic separation between channel and system
  • Internal temperature monitoring
  • Operating hour counter

Datasheet BEx IP67 Ex-i
Manual BEx IP20/IP67 Ex-i
IECEx
ATEX
North Amerika
DNV

Explosion protection
EPS 19 ATEX 1 219 X
EPS 22 UKEX 1 045 X
II 2(1) G Ex eb mb [ia Ga] IIC T4 Gb
II 2(1) D Ex tb [ia Da] IIIC T110°C Db

IECEx EPS 19.0093X
Ex eb mb [ia Ga] IIC T4 Gb
Ex tb [ia Da] IIIC T110°C Db

Class I, Division 2, Groups A, B, C, D
Class I, Zone 1, AEx eb mb [ia Ga] IIC T4 Gb
Class II, Division 2, Groups F, G
Zone 21, AEx tb [ia Da] IIIC T110°C Db

Power supply
Operating voltage UA/US DC 18...30V
Power supply module and sensors IS DC 450 mA
Power supply actuators IA DC 300 mA
Power loss max. 15 W
Reverse polarity protection Yes

Ambient conditions
Operating temperature -40°C ... +70°C
Storage temperature -40°C ... +80°C
Enclosure type (EN 60529) IP 20

Fieldbus data
Addressing Profinet DCP
Addressing Modbus DHCP
Transfer Rate 10/100 MBit/s
Delay at signal change < 10ms

IO channel
16 DI Namur
8 DO
8 DO(AIO)*
*individually adjustable as DO, AI, AO or Switching Mode

Mechanical data
Dimensions (LxBxH) 214 x 206 x 115mm
Installation position any position
Weight ca. 5400 g
Housing material Aluminium (electroplated)